Network models by region
Europe
Name
|
Version
|
Year
Published
|
Represented year
|
Region
|
Num. Substations or Buses
|
Num. Lines
|
Contains
|
Downloadable
|
Licence
|
SciGrid
|
0.1
|
2015
|
2015
|
Germany, but in principle whole world
|
479
|
765
|
Topology, Impedances
|
Yes
|
Apache Licence, Version 2.0
|
Bialek European Model
|
2
|
2013
|
2009
|
Continental Europe
|
1494 buses
|
2322
|
Topology, Impedances, Loads, Generators
|
Yes
|
Unclear
|
National Grid ETYS 2014 Model
|
|
2014
|
2014
|
Great Britain
|
365
|
316
|
Topology, Impedances, Loads, Generators
|
Yes
|
Unclear
|
Austrian Power Network Grid
|
|
2015
|
2015
|
Austria
|
|
~100
|
Topology, Impedances
|
Yes
|
Unclear
|
ENTSO-E STUM
|
|
|
2020?
|
Continental Europe?
|
1000s
|
1000s
|
Topology, Impedances
|
Requires registration
|
Unclear
|
SciGrid
SciGrid is a project started in 2014 and running for three years to develop an open and free model of the European transmission network. It is carried out by NEXT ENERGY - EWE Research Centre for Energy Technology, an independent non-profit institute at the University of Oldenburg, Germany, and funded by the German Ministry of Education.
Bialek European Model
The 2nd version of the Bialek European Model is downloadable as an Excel file and in the format of the proprietary modelling software PowerWorld. The model covers voltages from 110 kV (a single line in the Balkans) up to 380 kV.
The 1st version was released in 2002-2004 and is no longer available (see Archive mirror). The 1st version did not contain the Balkans region.
The methodology and validation for the 1st version of the model can be found in the paper Approximate model of European interconnected system as a benchmark system to study effects of cross-border trades by Zhou and Bialek, 2005.
National Grid Model
National Grid Electricity Ten Year Statement 2014 Model
Austrian Power Network Grid Model
Austrian Power Network Grid
ENTSO-E STUM
ENTSO-E makes available a model of the continental European system. Registration is required to download it on the ENTSO-E STUM page.
ENTSO-E Initial Dynamic Model of Continental Europe
ENTSO-E Initial Dynamic Model of Continental Europe
Requires registration. Can model "the main frequency response of the system as well as the main inter-area oscillation modes".
Global
OpenStreetMap
The global OpenStreetMap (OSM) power grid data is visible at ITO World Electricity Distribution and Enipedia has nightly extracts of the power grid from OSM.
See IRENA News Announcement
Non-Region Specific
RWTH Aachen Transmission Expansion Problem Benchmark Case
RWTH Aachen has published A Benchmark Case for Network Expansion, which is "derived from the IEEE 118 bus network and modified in accordance with European standards such as a nominal frequency of 50Hz, the use of conventional voltage levels, and conductor dimensions."
Registration is required to download the model.
The paper describing the model is A benchmark case for network expansion methods, 2015.
Other lists of network models
Enipedia list
Edinburgh University list
Free software for power system analysis
PyPower in Python
PowerGAMA in Python
MATPOWER in Matlab or Octave
OpenDSS in Pascal?
PSAT in Matlab or Octave
Other lists of power system analysis software
http://www.openelectrical.org/wiki/index.php?title=Power_Systems_Analysis_Software
https://nkloc.wordpress.com/2011/11/11/power-system-simulation-software-list/
Typical transmission line electrical parameters
European 50 Hz transmission
The main European alternating current (AC) electricity system is operated at 50 Hz. (Other networks, such as those for electrified trains, operate at other frequencies and some transmission lines use direct current.)
On the continent AC transmission voltages are typically 220 kV or 380 kV (sometimes quoted as 400 kV, since network operators often run their grid above nominal voltage to reduce network losses).
220 kV overhead lines are typically configured with a bundle of 2 wires per phase with wires of cross-section Al/St 240/40.
380 kV overhead lines are typically configured with a bundle of 4 wires per phase with wires of cross-section Al/St 240/40.
We now list the impedances for the lumped pi model of the transmission lines.
Electrical properties for single circuits
Voltage level (kV)
|
Type
|
Conductors
|
Series resistance (Ohm/km)
|
Series inductance (Ohm/km)
|
Shunt capacitance (nF/km)
|
Current limit (A)
|
220
|
Overhead line
|
2-wire-bundle Al/St 240/40
|
0.06
|
0.301
|
12.5
|
1290
|
380
|
Overhead line
|
4-wire-bundle Al/St 240/40
|
0.03
|
0.246
|
13.8
|
2580
|
In the table the current limit is calculated as 645 A per wire at an outside temperature of 20 degrees Celsius.
Sources for the electrical parameters:
Oeding and Oswald Elektrische Kraftwerke und Netze, 2011, Chapter 9
See also comparable parameters in the DENA Distribution Network Study, 2012, Table 5.6 and KIT Electrical Parameters Reading Sample, 2013.
Combining electrical parameters for multiple circuits
In the table above, the impedances are quoted for a single circuit. The resistance and inductances are in series, so decrease proportional to the number of parallel circuits (roughly - the geometry changes mean the series inductances is slightly modified). Similarly the capacitance is in shunt so increases proportional to the number of parallel circuits (again, roughly because of changing geometry).